Duct sizing calculator

Enter airflow and friction rate to get the round duct size, air velocity and rectangular equivalents. At 0.08 friction, a 6" metal duct carries about 95 CFM and an 8" about 205 CFM.

Help me find my friction rate
Available static pressure 0.14 in. w.c. ÷ 250 ft × 100 = 0.056 friction rate.
400 CFM · flex, fully stretched · 0.08 friction
12" round
509 fpm velocity · carries up to about 525 CFM
Exact size needed: 10.8"
Shop 12" flex duct

Airflow by duct size at 0.08 friction

Round sizeSheet metal (CFM)Flex, stretched (CFM)Flex, typical (CFM)
4"353025
5"605040
6"958565
7"145125100
8"205180145
9"280245195
10"370325260
12"605525420
14"905790630
16"12901125895

Calculated with the standard friction equation for galvanized duct (ASHRAE fundamentals), with flex multipliers of 1.3× (stretched) and 2× (typical install). Use it for estimates; a Manual D design is the final word.

Sizing a whole house?

The duct layout planner sizes every branch, the trunk and the returns from a few questions, then builds your parts list.

Open the layout planner

Duct sizing questions

How do I size a duct for a given CFM?

Pick a design friction rate (usually 0.06 to 0.10 inches of water column per 100 feet for homes), then find the round diameter that carries your CFM at that friction rate. At 0.08, a 6" metal duct carries about 95 CFM, an 8" about 205 CFM and a 10" about 370 CFM. Round up to the next standard size.

What friction rate should I use for residential duct design?

Manual D calculates it from the blower's available static pressure, minus the losses of the coil, filter, registers and grilles, divided by the total effective length of the longest run. Most homes land between 0.06 and 0.10. If you don't know it, 0.08 is a common starting point for an estimate.

How much CFM per ton of air conditioning?

About 400 CFM per ton is the standard design airflow. In humid climates many designers use 350 CFM per ton so the coil removes more moisture.

Does flex duct need to be bigger than metal duct?

Yes. Fully stretched flex has roughly 30% more friction than smooth metal, so it often needs the next size up. Flex that sags or is compressed can have twice the friction or more.

What air velocity is too high in ducts?

For quiet residential systems, keep supply trunks under about 900 feet per minute, and branch ducts and returns under about 700 feet per minute.

How do I convert round duct to rectangular?

Use the equivalent-diameter formula: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. For example, a 10" round duct is about equal to a 12 × 8 rectangular duct.